1.1.2.5 HRGF Detection Flex Operand States
Each breaker has 3 different states shown in
. Each one of them corresponds to a
different bit in the data item.
Table 1-10 HRGF Detection status bit field
The breaker states for all 30 breakers span across 6 consecutive modbus registers as shown in
PLC Interface (Read/Write) on page 110
for memory locations.
Table 1-11 HRGF Detection status offsets
Bit
Value
0
Alarm Dropout
1
Alarm Pickup
2
Alarm Operated
Breaker Number
Register
Offset
Bit Offset
Notes
Breaker 1
0
0
Breaker 2
0
3
Breaker 3
0
6
Breaker 4
0
9
...
...
...
...