background image

Modbus Memory Map

40

3

0036

Reserved

---

---

---

F001

0

Installation (Read/Write Setting)

0080

CPU ID

0 to 1

---

1

F717

0 (CCPU A)

0081

CPU Commissioned

0 to 1

---

1

F102

0 (Disabled)

0082

CPU Name

---

---

---

F200

“UNNAMED”

0096

System Frequency

50 to 60

Hz

10

F001

60

0097

Phase Rotation

0 to 1

---

1

F106

0 (ABC)

Clock (Read/Write Setting)

00E0

RTC Set Time

0 to 4294967295

---

1

F050

0

Clock (Read Only)

00E2

Date Time Changed

0 to 4294967295

---

1

F050

0

Communications (Read/Write Setting)

00EC

External Ethernet IP Address

0 to 4294967295

---

1

F003

3232235876

00EE

External Ethernet IP Subnet Mask

0 to 4294963200

---

1

F003

4294967040

00F0

External Ethernet Gateway IP Address

0 to 4294967295

---

1

F003

0

00F2

Reserved (5 items)

---

---

---

F001

0

Event Recorder (Read Only)

0150

Events Since Last Clear

0 to 4294967295

---

1

F003

0

0152

Number of Available Events

0 to 4294967295

---

1

F003

0

0154

Event Recorder Last Cleared Date

0 to 4294967295

---

1

F050

0

Modbus File Transfer (Read/Write)

0156

Name of file to read

---

---

---

F204

(none)

Modbus File Transfer (Read Only)

017E

Character position of current block within
file

0 to 4294967295

---

1

F003

0

0180

Size of currently-available data block

0 to 65535

---

1

F001

0

0181

Block of data from requested file (122 items)

0 to 65535

---

1

F001

0

Modbus File Transfer Area 2 (Read/Write)

01FB

Name of file to read

---

---

---

F204

(none)

Modbus File Transfer Area 2 (Read Only)

0223

Character position of current block within
file

0 to 4294967295

---

1

F003

0

0225

Size of currently-available data block

0 to 65535

---

1

F001

0

Advertising