25
1.1.2.16 Summation MSGF Zone Flex Operand States
Each zone has 7 different states shown in
. Each one of them corresponds to a different
bit in the data item.
Table 1-32 Summation MSGF Zone status bit field
The zone states for both zones reside in a single modbus register as shown in
Interface (Read/Write) on page 110
for memory locations.
Table 1-33 Summation MSGF Zone status offsets
Bit
Value
0
Trip Dropout
1
Alarm Dropout
2
Trip Pickup
3
Alarm Pickup
4
Trip Operated
5
Alarm Operated
6
Trip Restrained
Zone Number
Register
Offset
Bit Offset
Notes
Zone 1
0
0
Zone 2
0
8