1.1.2.2 Bus Differential Flex Operand States

Each zone has 6 different states shown in

Table 1-4

. Each one of them corresponds to a different bit

in the data item.

Table 1-4 Bus Differential status bit field

The zone states for all 4 relay instances span across 2 consecutive modbus registers as shown in

Table 1-3

. See

PLC Interface (Read/Write) on page 110

for memory locations.

Table 1-5 Bus Differential status offsets

Bit

Value

0

Trip Dropout

1

Alarm Dropout

2

Trip Pickup

3

Alarm Pickup

4

Trip Operated

5

Alarm Operated

6

Backup Trip Operated

Zone Number

Register
Offset

Bit Offset

Notes

Zone 1

0

0

Zone 2

0

7

Zone 3

0

14

This zone’s information spans
over two adjacent registers

Zone 4

1

5

1

12

Bits from 12 thru 15 are not used
and shall always be set to 0