GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual

Page 64

Advertising
background image

Modbus Memory Map

64

3

3839

SRC X HRGF Ground Resistance

5 to 500

---

1

F001

5

383A

SRC X HRGF CT Rating

10 to 10

---

1

F001

10

383B

Reserved (8 items)

---

---

---

F001

0

3843

SRC X High Curr Trigger Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

3844

SRC X High Curr Trigger Alarm Pickup Set-
ting

0.1 to 9

---

0.1

F001

20

3845

SRC X High Curr Trigger Alarm Delay Setting

1 to 120

---

1

F001

12

3846

SRC X High Curr Trigger Alarm WFC Enable

0 to 1

---

1

F102

0 (Disabled)

3847

SRC X High Curr Trigger Alarm Max WF

0 to 30

---

1

F001

15

Source Settings (Read Only) (30 modules)

3848

SRC X High Curr Trigger Alarm WF Triggered

0 to 30

---

1

F001

0

Source Settings (Read/Write Command) (30 modules)

3849

SRC X High Curr Trigger Alarm WF Count
Reset

0 to 1

---

1

F126

0 (No)

384A

SRC X Settings Reserved (40 items)

---

---

---

F001

0

3872

...Repeated for module number 2

3926

...Repeated for module number 3

39DA

...Repeated for module number 4

3A8E

...Repeated for module number 5

3B42

...Repeated for module number 6

3BF6

...Repeated for module number 7

3CAA

...Repeated for module number 8

3D5E

...Repeated for module number 9

3E12

...Repeated for module number 10

3EC6

...Repeated for module number 11

3F7A

...Repeated for module number 12

402E

...Repeated for module number 13

4000

...Repeated for module number 14

4196

...Repeated for module number 15

424A

...Repeated for module number 16

42FE

...Repeated for module number 17

43B2

...Repeated for module number 18

4466

...Repeated for module number 19

Advertising