Integrator’s Guide

22

1.1.2.13 Phase Loss Flex Operand States

Each breaker has 6 different states shown in

Table 1-26

. Each one of them corresponds to a

different bit in the data item.

Table 1-26 Phase Loss status bit field

The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in

Table 1-27

. See

PLC Interface (Read/Write) on page 110

for memory locations.

Table 1-27 Phase Loss status offsets

Bit

Value

0

Alarm Pickup

1

Alarm Operated

2

Alarm Dropout

3

Trip Pickup

4

Trip Operated

5

Trip Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

6

Breaker 3

0

12

This breaker’s information spans
over two adjacent registers

Breaker 4

1

2

...

...

...