47

3

04E8

HRGF Location Alarm State

0 to 4294967295

---

1

F722

0

04EA

HRGF Location Alarm Ack

0 to 4294967295

---

1

F722

0

04EC

Reserved (28 items)

---

---

---

F001

0

0508

SRC X Node Ground CT Connected

0 to 4294967295

---

1

F722

0

050A

High Current Trigger Alarm State

0 to 4294967295

---

1

F722

0

050C

High Current Trigger Alarm Ack

0 to 4294967295

---

1

F722

0

050E

Reduced Let Thru Over 8 Hours Alarm State

0 to 4294967295

---

1

F722

0

0510

Reduced Let Thru Over 8 Hours Alarm Ack

0 to 4294967295

---

1

F722

0

0512

HRGF Location Contactor Operating Alarm
State

0 to 4294967295

---

1

F722

0

0514

HRGF Location Contactor Operating Alarm
Ack

0 to 4294967295

---

1

F722

0

0516

HRGF Location Trip Alarm State

0 to 4294967295

---

1

F722

0

0518

HRGF Location Trip Alarm Ack

0 to 4294967295

---

1

F722

0

Voltage (Read Only) (30 modules)

0542

Phase AG Voltage RMS

0 to 999999.999

V

0.001

F060

0

0544

Phase BG Voltage RMS

0 to 999999.999

V

0.001

F060

0

0546

Phase CG Voltage RMS

0 to 999999.999

V

0.001

F060

0

0548

Phase AB or AC Voltage RMS

0 to 999999.999

V

0.001

F060

0

054A

Phase BC or BA Voltage RMS

0 to 999999.999

V

0.001

F060

0

054C

Phase CA or CB Voltage RMS

0 to 999999.999

V

0.001

F060

0

054E

SRC X Voltage Reserved (30 items)

---

---

---

F001

0

056C

...Repeated for module number 2

0596

...Repeated for module number 3

05C0

...Repeated for module number 4

05EA

...Repeated for module number 5

0614

...Repeated for module number 6

063E

...Repeated for module number 7

0668

...Repeated for module number 8

0692

...Repeated for module number 9

06BC

...Repeated for module number 10

06E6

...Repeated for module number 11

0710

...Repeated for module number 12

Advertising