GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual

Page 63

Advertising
background image

63

3

3817

SRC X Breaker Percent Load Life

0 to 655.35

---

0.01

F001

0

Source Settings (Read Only) (30 modules)

3818

SRC X Percent Mechanical Life

0 to 655.35

---

0.01

F001

0

Source Settings (Read/Write Setting) (30 modules)

3819

SRC X Time Date Last Breaker Operation

0 to 4294967295

---

1

F050

0

381B

SRC X Time Date Initial Energization

0 to 4294967295

---

1

F050

0

Source Settings (Read Only) (30 modules)

381D

SRC X Breaker Service Hours

0 to 4294967295

---

1

F003

0

Source Settings (Read/Write Setting) (30 modules)

381F

Source Settings Reserved 6 (5 items)

---

---

---

F001

0

3824

SRC X UF Trip Enable

0 to 1

---

1

F102

0 (Disabled)

3825

SRC X UF Trip Pickup Setting

45 to 60

---

0.1

F001

450

3826

SRC X UF Trip Time Delay

0.1 to 600

---

0.1

F001

300

3827

SRC X UF Trip Blocking Voltage Enable

0 to 1

---

1

F102

0 (Disabled)

3828

SRC X UF Trip or Open setting

0 to 1

---

1

F727

1 (Trip and acti-

vate lockout)

3829

SRC X UF Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

382A

SRC X UF Alarm Pickup Setting

45 to 60

---

0.1

F001

450

382B

SRC X UF Alarm Time Delay

0.1 to 600

---

0.1

F001

150

382C

SRC X UF Alarm Blocking Voltage Enable

0 to 1

---

1

F102

0 (Disabled)

382D

SRC X OF Trip Enable

0 to 1

---

1

F102

0 (Disabled)

382E

SRC X OF Trip Pickup Setting

50 to 70

---

0.1

F001

500

382F

SRC X OF Trip Time Delay

0.1 to 600

---

0.1

F001

300

3830

SRC X OF Trip Blocking Voltage Enable

0 to 1

---

1

F102

0 (Disabled)

3831

SRC X OF Trip or Open setting

0 to 1

---

1

F727

1 (Trip and acti-

vate lockout)

3832

SRC X OF Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

3833

SRC X OF Alarm Pickup Setting

50 to 70

---

0.1

F001

500

3834

SRC X OF Alarm Time Delay

0.1 to 600

---

0.1

F001

150

3835

SRC X OF Alarm Blocking Voltage Enable

0 to 1

---

1

F102

0 (Disabled)

3836

SRC X HRGF Enable

0 to 1

---

1

F102

0 (Disabled)

3837

SRC X HRGF Pickup

0.1 to 10

---

0.1

F001

20

3838

SRC X HRGF Delay

0.5 to 5

---

0.1

F001

5

Advertising