Modbus Memory Map

66

3

4E3E

...Repeated for module number 13

4E5C

...Repeated for module number 14

4E7A

...Repeated for module number 15

4E98

...Repeated for module number 16

4EB6

...Repeated for module number 17

4ED4

...Repeated for module number 18

4EF2

...Repeated for module number 19

4F10

...Repeated for module number 20

4F2E

...Repeated for module number 21

4F4C

...Repeated for module number 22

4F6A

...Repeated for module number 23

4F88

...Repeated for module number 24

4FA6

...Repeated for module number 25

4FC4

...Repeated for module number 26

4FE2

...Repeated for module number 27

5000

...Repeated for module number 28

501E

...Repeated for module number 29

503C

...Repeated for module number 30

Synch Check Settings (Read/Write Setting) (12 modules)

505A

Synch Check Enable

0 to 1

---

1

F102

0 (Disabled)

505B

Synch Check V1 Source

0 to 29

---

1

F001

0

505C

Synch Check V2 Source

0 to 29

---

1

F001

0

505D

Synch Check Max Volt Diff

0 to 90

---

0.5

F001

0

505E

Synch Check Max Phase Diff

0 to 60

---

1

F001

0

505F

Synch Check Max Freq Diff

0 to 2

---

0.1

F001

0

5060

Synch Check Dead Max V1

5 to 50

---

1

F001

5

5061

Synch Check Live Min V1

50 to 100

---

1

F001

50

5062

Synch Check Dead MaxV2

5 to 50

---

1

F001

5

5063

Synch Check Live Min V2

50 to 100

---

1

F001

50

5064

Reserved (4 items)

---

---

---

F001

0

5068

Synch Check Dead Source Select

0 to 5

---

1

F176

0 (None)

Synch Check Settings (Read Only) (12 modules)

5069

Synch Check Status

0 to 65535

---

1

F001

0