1.1.2.10 Multi Point RELT Flex Operand States

This relay has 1 state shown in

Table 1-20

.

Table 1-20 Multi Point RELT status bit field

The relay state uses one modbus register as shown in

Table 1-21

. See

PLC Interface (Read/Write)

on page 110

for memory locations.

Table 1-21 Multi Point RELT status offsets

Bit

Value

0

Multipoint Reduced Let-Thru Mode On

Zone Number

Register
Offset

Bit Offset

Notes

RELT State

0

0

0

1

Bits from 1 thru 15 are not used
and shall always be set to 0