Modbus Memory Map

110

3

DB35

...Repeated for module number 254

DB37

...Repeated for module number 255

DB39

...Repeated for module number 256

PLC Interface (Read/Write)

DC00

PLC Input States (16 items)

0 to 65535

---

1

F500

0

PLC Interface (Read Only)

DC10

Virtual Input States (2 items)

0 to 65535

---

1

F500

0

DC12

Virtual Output States (30 items)

0 to 65535

---

1

F500

0

DC30

Contact Input States (8 items)

0 to 65535

---

1

F500

0

DC38

Contact Output States (8 items)

0 to 65535

---

1

F500

0

DC40

Breaker Control Flex Operand States (25
items)

0 to 65535

---

1

F500

0

DC59

Bus Differential Flex Operand States (2
items)

0 to 65535

---

1

F500

0

DC5B

Reserved (12 items)

---

---

---

F001

0

DC67

Ground Fault Flex Operand States (12 items)

0 to 65535

---

1

F500

0

DC73

High Current Flex Operand States (6 items)

0 to 65535

---

1

F500

0

DC79

Reserved (3 items)

---

---

---

F001

0

DC7C

High Current Transient Flex Operand States
(6 items)

0 to 65535

---

1

F500

0

DC82

HRGF Detection Flex Operand States (6
items)

0 to 65535

---

1

F500

0

DC88

HRGF Location Flex Operand States

0 to 65535

---

1

F500

0

DC89

IOC Flex Operand States (4 items)

0 to 65535

---

1

F500

0

DC8D

LT Overcurrent Flex Operand States (6 items)

0 to 65535

---

1

F500

0

DC93

MSGF Overcurrent Flex Operand States (2
items)

0 to 65535

---

1

F500

0

DC95

Multi Point RELT Flex Operand States

0 to 65535

---

1

F500

0

DC96

Over Frequency Flex Operand States (12
items)

0 to 65535

---

1

F500

0

DCA2

Over Voltage Flex Operand States (12 items)

0 to 65535

---

1

F500

0

DCAE

Phase Loss Flex Operand States (12 items)

0 to 65535

---

1

F500

0

DCBA

Power Reversal Flex Operand States (12
items)

0 to 65535

---

1

F500

0