GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual

Page 115

Advertising
background image

115

4

[6] VIRTUAL OUTPUTS (1-64)

[10] CONTACT OUTPUTS VOLTAGE DETECTED ( 1-64)

[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64)

[12] CONTACT OUTPUTS CURRENT DETECTED (1-64)

[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1-64)

[14] REMOTE INPUTS (1-32)

[28] INSERT (Via Keypad only)

[32]

END

[34] NOT (1 INPUT)

[36] 2 INPUT XOR (0)

[38] LATCH SET/RESET (2 INPUTS)

[40] OR (2-16 INPUTS)

[42] AND (2-16 INPUTS)

[44] NOR (2-16 INPUTS)

[46] NAND (2-16 INPUTS)

[48] TIMER (1-32)

[50] ASSIGN VIRTUAL OUTPUT (1 - 64)

[52] SELF-TEST ERROR (See F141 for range)

[56] ACTIVE SETTING GROUP (1-8)

[62] MISCELLANEOUS EVENTS (See F146 for range)

[64-127] ELEMENT STATES (Refer to Memory Map Element States Section)

F500

UINT16

PACKED BITFIELD











First register indicates I/O state with bits 0(MSB)-15(LSB) corresponding to I/0 state 1-16.
Second register indicates I/O state with bits 0-15 corresponding to I/0 state 17-32 (if
required). Third register indicates I/O state with bits 0-15 corresponding to I/0 state 33-
48 (if required). Fourth register indicates I/O state with bits 0-15 corresponding to I/0
state 49-64 (if required). The number of registers required is determined by the specific
data item.
A bit value of 0 = Off, 1 = On

F701

BITFIELD

SRCx Node Internal Diagnostics Bit Mask

0

Power-on Self Test Error Detected

1

Built-In-Test Error Detected

2

Invalid Data Detected

3

Jamb sync occurred over threshold

4

Invalid node configuration detected