GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual

Page 61

Advertising
background image

61

3

37BF

SRC X PT Source Node Identifier

0 to 29

---

1

F001

0

Source Settings (Read/Write Setting) (30 modules)

37C0

SRC X Breaker Connection

0 to 1

---

1

F712

0 (Forward)

37C1

Reserved (2 items)

---

---

---

F001

0

37C3

Source Settings Reserved (15 items)

---

---

---

F001

0

37D2

SRC X PT Rating

0 to 6

---

1

F719

0 (None)

37D3

SRC X UV Trip Enable

0 to 1

---

1

F102

0 (Disabled)

37D4

SRC X UV Trip Curve Type

0 to 1

---

1

F726

1 (Constant time

curve)

37D5

SRC X UV Trip Pickup Setting

10 to 95

---

1

F001

50

37D6

SRC X UV Trip Time Delay

0.5 to 600

---

0.5

F001

300

37D7

SRC X UV Trip Phase Requirement

1 to 3

---

1

F001

1

37D8

SRC X UV Trip Block Volt Enable

0 to 1

---

1

F102

0 (Disabled)

37D9

SRC X UV Trip Block Volt Setting

5 to 75

---

1

F001

5

37DA

SRC X UV Trip Open or Trip Setting

0 to 1

---

1

F727

1 (Trip and acti-

vate lockout)

37DB

SRC X UV Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

37DC

SRC X UV Alarm Curve Type

0 to 1

---

1

F726

1 (Constant time

curve)

37DD

SRC X UV Alarm Pickup Setting

10 to 95

---

1

F001

50

37DE

SRC X UV Alarm Time Delay

0.5 to 600

---

0.5

F001

150

37DF

SRC X UV Alarm Phase Requirement

1 to 3

---

1

F001

1

37E0

SRC X UV Alarm Block Volt Enable

0 to 1

---

1

F102

0 (Disabled)

37E1

SRC X UV Alarm Block Volt Setting

5 to 75

---

1

F001

5

37E2

SRC X OV Trip Enable

0 to 1

---

1

F102

0 (Disabled)

37E3

SRC X OV Trip Pickup Setting

105 to 125

---

1

F001

120

37E4

SRC X OV Trip Time Delay

0.5 to 600

---

0.5

F001

300

37E5

SRC X OV Trip Phase Requirement

1 to 3

---

1

F001

1

37E6

SRC X OV Trip Open or Trip Setting

0 to 1

---

1

F727

1 (Trip and acti-

vate lockout)

37E7

SRC X OV Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

37E8

SRC X OV Alarm Pickup Threshold

105 to 125

---

1

F001

120

37E9

SRC X OV Alarm Time Delay

0.5 to 600

---

0.5

F001

150

37EA

SRC X OV Alarm Phase Requirement

1 to 3

---

1

F001

1

Advertising