GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual

Page 70

Advertising
background image

Modbus Memory Map

70

3

64C0

MSGF ZSI Zone 1 GRP X Tier Settings (16
items)

0 to 3

---

1

F733

0 (ZSI Tier 0)

64D0

MSGF ZSI Zone 2 GRP X Tier Settings (16
items)

0 to 3

---

1

F733

0 (ZSI Tier 0)

64E0

MSGF ZSI Zone 3 GRP X Tier Settings (16
items)

0 to 3

---

1

F733

0 (ZSI Tier 0)

64F0

MSGF ZSI Zone 4 GRP X Tier Settings (16
items)

0 to 3

---

1

F733

0 (ZSI Tier 0)

6500

MSGF ZSI Reserved (16 items)

---

---

---

F001

0

6510

...Repeated for module number 2

6560

...Repeated for module number 3

65B0

...Repeated for module number 4

Zone X MSGF Settings (Read/Write Setting) (4 modules)

6600

Zone X MSGF Trip Pickup Setting (16 items)

30 to 1200

---

10

F001

1200

6610

Zone X MSGF Alarm Pickup Setting (16 items)

30 to 1200

---

10

F001

1200

6620

Zone X MSGF Trip Delay Band Setting (16
items)

0 to 6

---

1

F735

2 (BAND 3)

6630

Zone X MSGF Alarm Delay Band Setting (16
items)

0 to 6

---

1

F735

2 (BAND 3)

6640

Zone X MSGF Trip I2T Curve (16 items)

0 to 1

---

1

F102

0 (Disabled)

6650

Zone X MSGF Alarm I2T Curve (16 items)

0 to 1

---

1

F102

0 (Disabled)

6660

Zone X MSGF Trip Enabled (16 items)

0 to 1

---

1

F102

0 (Disabled)

6670

Zone X MSGF Alarm Enabled (16 items)

0 to 1

---

1

F102

0 (Disabled)

6680

Zone X MSGF Backup Enabled (16 items)

0 to 1

---

1

F102

0 (Disabled)

6690

Zone X MSGF Backup Time Date Enabled (16
items)

0 to 1

---

1

F102

0 (Disabled)

66A0

Zone X MSGF Trip or Open

0 to 1

---

1

F727

0 (Open and

don't activate

lockout)

66A1

Zone X MSGF Reserved (16 items)

---

---

---

F001

0

66B1

...Repeated for module number 2

6762

...Repeated for module number 3

6813

...Repeated for module number 4

Zone X BD Settings (Read/Write Setting) (4 modules)

68C4

Zone X BD Trip Pickup Setting (16 items)

100 to 22000

---

100

F001

1200