A Series

®

Lighting Controller LCD Programmer

Chapter 8 – Lighting Group Menu

29

5.

Press the

Fn

key to change the panel number (if a

reference to the remote panel photocell inputs is
needed) with the numeric keys. Press

OK

to accept

the new panel number.

6.

The object type flashes. Press

OK

to accept the

object type.

7.

The object instance flashes. Use the arrow keys to
change the instance number.

Press

OK

to accept the changes and switch to the

Lights On display:

8.

Press

OK

to adjust the Lights On Yes/No value.

9.

Use the arrow keys to change the setting and press

OK

to accept it.

The Lights On feature enables or disables
photocell control for turning the lighting group
on. If no change is required, press the arrow key to
go to the Lights Off menu.

10.

If the input is an AI and Lights On is enabled,
then On When LT/EQ scrolls across the display.
Press

OK

to adjust this value using the number

keys. Press

OK

to accept the change. The analog

inputs are defined as percentages. (For example, if
the jumper on the controller is set for 5 V, then the
range 0–5 V range is indicated as 0–100%)

The display may show the following:

11.

Press

OK

to adjust the Lights Off Yes/No value.

12.

Use the arrow keys to change the setting and press

OK

to accept the change.

The Lights Off feature enables or disables
photocell control for turning the lighting group
Off.

13.

If the input is an AI and Lights Off is enabled,
then the Off When GT/EQ scrolls across the
display. Press OK to adjust this value using the
number keypad and press

OK

to accept any

changes.

Flashing

Flashing

Flashing

Flashing

Flashing

Flashing