A Series
®
Lighting Controller LCD Programmer
Chapter 8 – Lighting Group Menu
29
5.
Press the
Fn
key to change the panel number (if a
reference to the remote panel photocell inputs is
needed) with the numeric keys. Press
OK
to accept
the new panel number.
6.
The object type flashes. Press
OK
to accept the
object type.
7.
The object instance flashes. Use the arrow keys to
change the instance number.
Press
OK
to accept the changes and switch to the
Lights On display:
8.
Press
OK
to adjust the Lights On Yes/No value.
9.
Use the arrow keys to change the setting and press
OK
to accept it.
The Lights On feature enables or disables
photocell control for turning the lighting group
on. If no change is required, press the arrow key to
go to the Lights Off menu.
10.
If the input is an AI and Lights On is enabled,
then On When LT/EQ scrolls across the display.
Press
OK
to adjust this value using the number
keys. Press
OK
to accept the change. The analog
inputs are defined as percentages. (For example, if
the jumper on the controller is set for 5 V, then the
range 0–5 V range is indicated as 0–100%)
The display may show the following:
11.
Press
OK
to adjust the Lights Off Yes/No value.
12.
Use the arrow keys to change the setting and press
OK
to accept the change.
The Lights Off feature enables or disables
photocell control for turning the lighting group
Off.
13.
If the input is an AI and Lights Off is enabled,
then the Off When GT/EQ scrolls across the
display. Press OK to adjust this value using the
number keypad and press
OK
to accept any
changes.
Flashing
Flashing
Flashing
Flashing
Flashing
Flashing