A Series

®

Lighting Controller Programmer

Chapter 8 – Lighting Group Menu

30

1 4 .

Use the Arrow keys to scroll and review the
changes or press

ESC

to return to the Photocell

submenu.

Override

The Override function is used to command a Lighting
Group On from the Off condition for a set time, and
then to command it Off by relinquishing control.
Override references can be BV, MI, BI, MV, both local
and remote. Any reference to BI and MV should be ignored.
The Override time can be set from 1 to 240 minutes.
The default value is 120 minutes.

Viewing Override

Use the following procedure to view override times:

1.

Navigate to the desired lighting group and press

OK

.

2.

Press the

Fn

key and use the arrow keys to navigate

to the Override menu:

3.

Press

OK

to display the Override input:

4.

Press the arrow keys to view the Override time
(1–240 minutes):

5.

Press

ESC

to return to the Override submenu.

Adding an Override Input

Use the following procedure to add an Override input:

1.

Navigate to the desired lighting group and press

OK

.

2.

Press the

Fn

key and use the arrow keys to navigate

to the Override menu:

3.

If there are currently no inputs, the following
display appears:

4.

Press

OK

and then use the arrow keys to select the

object type (BV, MI).

or

5.

Press the

Fn

key to edit the panel number. Press

the numeric keys to change the panel number (if a

Flashing

Flashing