A Series

®

Lighting Controller Programmer

Chapter 8 – Lighting Group Menu

32

10.

Press

OK

to edit the Override time.

11.

Use the arrow keys or the number keypad to adjust
the time, up to 240 minutes:

12.

Press

OK

to accept the changes.

13.

Press

ESC

to return to the Override submenu.

Groups

The Groups function is used for common areas so that
lights stay on when any one of the nested Lighting
Groups is on. Lights stay on until all the nested groups
are OFF and the off time delay times out. Note that if a
Schedule, Photocell, Astro, or Override turns the group
on, then the group remains on.

Viewing a Group

1.

Navigate to the Lighting Group menu.

2.

Press

OK

to display the first Lighting Group and

use the arrow keys to navigate to the desired
group.

3.

Press

OK

and AUTO starts to flash:

4.

Press the

Fn

key and press the down arrow key five

times to reach the Groups submenu:

5.

Press

OK

to display the Group Off time:

6.

Use the arrow keys to continue to scroll and view
all available groups.

Changing the Group Off Time

Use the following procedure to adjust the group Off
time.

1.

Navigate to the Groups submenu as in the previous
procedure.

2.

Press

OK

to display the Group Off time.

3.

Press

OK

to edit the Group Off Time:

4.

Use the number keys to adjust the Group Off time,
and then press

OK

.

Flashing

Flashing

Flashing

Flashing

Advertising