A Series

®

Lighting Controller LCD Programmer

Chapter 13 – Event Menu

49

3.

Press

OK

to display the current buffer size:

4.

To edit the buffer press

OK:

5.

Use the numeric keypad or arrow keys to enter the
new buffer size.

6.

Press

OK

to display Device Status. Device status

consists of dead battery, reset device, device
offline, or undervoltage.

7.

Do either of the following:

• Use the arrow keys to scroll to the next category

if no change is required.

• To edit press

OK

. Press the arrow key to adjust

Yes or No, and then press OK to accept the
change.

8.

The Time Change display appears next:

9.

Do either of the following:

• Use the arrow keys to scroll to the next category

if no change is required.

• To edit press

OK

. Press the arrow key to adjust

Yes or No and then press

O K

to accept the

change.

1 0 .

The Lighting Alarms display is next. Lighting
alarms consists of breaker trip and command
failure.

11.

Do either of the following:

• Use the arrow keys to scroll to the next category

if no change is required.

• To edit press

OK

. Press the arrow key to adjust

Yes or No and then press

O K

to accept the

change.

1 2 .

The Lighting Status display appears. Lighting
status consists of status on and status off.

13.

Do either of the following:

• Use the arrow keys to scroll to the next category

if no change is required.

• To edit press

OK

. Press the arrow key to adjust

Yes or No and then press

O K

to accept the

change.

Flashing