A Series

®

Lighting Controller LCD Programmer

Chapter 13 – Event Menu

47

The Event menu is used to view and reset event entries
and to set the size of event buffer. They are also used to
enable and disable the alarm output for different
conditions, such as device status, time change, lighting
alarm, and lighting status and to acknowledge the
alarm output. Acknowledging the alarm output turns
off the alarm relay, which is triggered in response to the
device status change (device goes offline, device reset,
dead battery, and undervoltage), time change (time of
the controller changes), lighting status (breaker turns
on or off), and lighting alarms (breaker is tripped or
there is a command failure).

The events listed in Table 3 are displayed on the
Programmer. Events are displayed beginning with the
most recent events. A maximum of 2000 events can be
viewed at a time.

Event

Display

Alarm

ALARM

Alarm Acknowledged

ALARM ACK

Dead Battery

DEAD BATT

Dead Battery Restored

DEAD BATT RESTORED

Command Failure

CMD FAIL

Command Fail Restored

CMD FAIL RESTORED

Status ON

STATUS ON

Status OFF

STATUS OFF

Under Voltage

UNDER VOLT

Under Voltage Restored

UNDER VOLT RESTORED

Reset

DEV RESET

Time / Date change

TIME CHG

DB Load

DB LOAD

DB Save

DB SAVE

DB Clear

DB CLEAR

Lnk Online

DEV ONLINE

Lnk Offline

DEV OFFLINE

Breaker Trip

BREAKER TRIP

Breaker Trip Restored

BREAKER TRIP RESTORED

No events occurred

NONE

Table 3. Events captured in the CE log.

Acknowledging an Alarm

Use the following procedure to acknowledge an alarm:

1.

Press any key on the keypad to silence the alarm.

2.

Press

OK

and then login using the appropriate

password.

3.

Use the arrow keys to navigate to the Event menu:

4.

Press

OK

to reach the following display:

5.

Press

OK

and AUTO flashes:

6.

Press the

A/M

key to put into manual mode and

press the arrow key until ACK is displayed. Press

OK

to acknowledge the alarm.

7.

Press

ESC

to exit to the Event submenu.

8.

The Alarm Acknowledge submenu returns to the
default auto mode without further user input.

Displaying the CE Log –
Viewing Events

Use the following procedure to view an event:

1.

Navigate to the Event menu with the arrow keys: