Battery Temp Sensor

The Battery Temp connector attaches the battery temperature sensor to the Alpha Micro to monitor the battery

temperature. The charging voltage is temperature dependant. The Alpha Micro’s microprocessor adjusts the

charging voltage for optimum charging.
The sensor MUST be attached to the Alpha Micro for normal operation. Firmly attach the sensor end to the centre

battery’s case with high-strength flameproof tape such as duct tape as shown in “Wiring the External Batteries”

section. If the sensor isn't attached, a “Temperature Probe Unplugged” alarm will appear on the LCD.

9

User Input C7

This optically isolated input lets you attach an external switch panel for remote control of the

Alpha Micro.

• 19 (S1):

Shorting this contact to 22 (C) starts the Alpha Micro’s self test.

• 20 (S2):

Shorting this contact to 22 (C) activates an alarm.

• 21 (S3):

Shorting this contact to 22 (C) disables the AC output. There is no AC output power, the LCD

display shows “SHUTDOWN”, but the Alpha Micro is still energized. A manual restart is required to put the

Alpha Micro back to normal operation.

• 22 (C):

Isolated return for contacts S1, S2 and S3.

USER INPUT

C7

19

S1 S2 S3

C

20 21

22

Figure 4 — User Input Layout

10

ATS C8

When the

Alpha Micro

is in Inverter mode, the normally open relay closes (Figure 5), sending 48 VDC or 24 VDC

from the batteries to this dry contact.
This contact can be used to power any external logic circuits or loads when the Alpha Micro is in Inverter mode.

Figure 5 — ATS Contact

Microprocessor

+

48VDC or 24VDC

from the batteries