017-237-B0 Rev A

6.9.6 Setting the Timer Contact

The front panel’s timer contact can be programmed to suit your application. See "Contacts C1 to C6” and "Pro-

gramming the Dry Contacts and the Clock". The table below explains how.

Table M — Setting the Timer Contact

Enter command

UPS display

Description

Displaying the Timer

timer and press Enter

*timer=02:00:00

Returns the value of timer

timer1 and press Enter

*timer1=02:00:00

Returns the value of timer1

timer2 and press Enter

*timer2=02:00:00

Returns the value of timer2

Setting

the T

imer

timer=00:01:00 and press

Enter

*timer=00:01:00

Sets the value of timer1 to 60

seconds.

timer=00:01:00 and press

Enter

*timer=120

timer1=00:01:00 and press

Enter

*timer1=00:01:00

Sets the value of timer1 to 60

seconds.

timer1=120

and press

Enter

*timer1=120

timer2=00:01:00 and press

Enter

*timer2=00:01:00

Sets the value of timer2 to 60

seconds.

timer2=120

and press

Enter

*timer2=120

default and press Enter

*default

Resets the timer to the factory

default of 02:00:00 (2 hours);

and resets contacts C1 to C5 to

the factory default settings.See

“Programming the Dry Contacts”.

Note: In the above example, the default timer setting of 2 hours is used.

* Indicates that the Alpha Micro has responded to the command you entered.

† Time can be entered in units of 0.5 second; e.g. 120 units of 0.5 seconds = 60 seconds. However, it is more intui-

tive to enter time in the hh:mm:ss format, such as 00:01:00 for 1 minute or 60 seconds in the above example.