Procedure – Alpha Technologies Micro, Micro XL, Micro XL3 UPS User Manual

Page 50

Advertising
background image

017-237-B0 Rev A

48

6.9.10 100-Event Log

Up to 100 events are stored in the Alpha Micro’s log. If more than 100 events occur, the oldest is over-written.

Procedure

1. To see the log, type event (all lower case) and press Enter. The events are listed starting with the most

recent and appear as: If less than 100 events occurred, the last entry will appear as:

See below for details on these
readouts.

eventX=12/25/99 01:45:59 0000000000000000, 0000000000000000, 000

Event Date Time

Alarm

Fault

Mode

Date & Time formats depend
on selected display format

Alarm: When the following bits show a 1,

the following alarms are displayed.

Self Test

Fault: When the following bits show a 1,

the following faults are displayed..

Table O — Event Codes

Code

Mode

Code

Mode

Code

Mode

000

Standby

003

Boost 1

006

Inverter

001

Line

004

Buck 1

009

Shutdown

002

Boost 2

005

Buck 2

010

Bypass

2. If less than 100 events occurred, the last entry will appear as:

3. To clear the log, type eventclr and press Enter. It takes the Alpha Micro 30 seconds to clear the log. Do not

enter any other commands during this time.

4. To see a specific event, type eventX where X is from 1 to 100 and press Enter. To see a range of events (for

example, events 20 to 30), type eventX-X where X are events from 1 to 100 and press Enter. To clear the

log, type eventclr and press Enter. It takes the Alpha Micro 30 seconds to clear the log. Do not enter any

other commands during this time.

5. To see a specific event, type eventX where X is from 1 to 100 and press Enter. To see a range of events (for

example, events 20 to 30), type eventX-X where X are events from 1 to 100 and press Enter.

eventX=00/00/00 00:00:00 0000000000000000, 0000000000000000, 000