3. RS-232 HyperTerminal – the Temperature trigger function can be assigned to any available dry contacts as

described in "Programming the Dry Contacts" (e.g. c1=11, where 11 is the assigned index for the Temperature

trigger function.)

After establishing an RS-232 connection with the Alpha Micro at the HyperTerminal screen prompt, type

Temp and press Enter to display the current temperature setting Alpha Micro returns *temp=20). To change

the value to +35°C, type temp=35 and press Enter. The Alpha Micro returns *temp=35 as confirmation.

Figure 37 — Temperature trigger function via HyperTerminal

Programmable Dry Contact Time of Day Action
You can assign a dedicated timer to a dry contact. Upon entering the Inverter operating mode, the timer is acti-

vated and begins to count down from a user defined value. When the timer reaches zero, the programmed dry

contact relay will be activated (Status = ON).

Inverter

mode

entered

Dry contact

activates when timer

counts down to zero

Timer

starts to

count down

Microprocessor

Figure 38 — Programmable Timer Operation