5 making measurements, 1 procedure – Alpha Technologies Micro, Micro XL, Micro XL3 UPS User Manual

Page 37

Advertising
background image

35

017-237-B0 Rev A

6.5 Making Measurements

The System Status menu lets you make measurements of various Alpha Micro inputs, outputs, temperatures and

other values. You can also use the Alpha UPS Monitor to make these measurements. See “Alpha UPS Monitor”.

6.5.1 Procedure

1. From the Logo screen go to the System Status menu.

2. Press the SELECT button to enter the submenu (Table E).

3. Press the SCROLL button to move between items in the submenu. When you reach the item you want

to measure, stop pressing the button. The measurement is automatically displayed on the LCD. It is

automatically updated every 0.5 second.

Table E — System Status Menu

LCD display

Meaning

Description

VIN

Input Voltage

The line input voltage into the Alpha Micro

VOUT

Output Voltage

The Alpha Micro’s output voltage (true RMS).

IOUT AC

Output Current

(AC)

The Alpha Micro’s AC output current (true RMS).

BATT TEMP

Battery

Temperature

The battery’s temperature (°C).

FREQ IN

Input Frequency

The frequency of line power into the Alpha Micro (Hz).

OUTPUT PWR

Output Power

The Alpha Micro’s output power in VA (true RMS).

BATT VOLT

Battery Voltage

The battery’s output voltage (VDC).

CHGR CUR

Charger Current

The Alpha Micro’s battery charging current is set to this value (Amps).

SHED TIMER1

Amount of

time until the

dry contact is

activated.

The factory default dry contact for this setting is contact C4. SHED TIMER2 and

SHED TIMER3 can be field programmed. See “Setting the Timer Contact”. This 

display shows the amount of time left in seconds until the contact is activated.

The factory default setting is 2 hours, but this can be changed as shown in

"Programming the Dry Contacts and the Clock".

SHED TIMER2
SHED TIMER3

MAC Address

CXC MAC

The CXC MAC address will be displayed.

IP Address

CXC IP

The CXC IP will be displayed.

kWh

kW Meter

The accumulated output power will be displayed.

Remain Tm

Remaining

Battery Runtime

The remaining runtime of the battery will be displayed.

Serial Number

Unit Serial

Number

The unit serial number of the Alpha Micro will be displayed.

VERSION

Software Version

The software version used in this Alpha Micro.

Advertising