A typical application of this timer controlled dry contact function is to control a traffic light. When the grid power

fails, the Alpha Micro goes into the Inverter mode and continues supplying backup power to the traffic light. Since

the batteries supplying the backup power have limited capacity, a timer controlled dry contact is usually config-

ured to switch the traffic light into the flashing amber or flashing red mode after a user-defined period to conserve

battery power. This setup works fine during non rush hour traffic, but during rush hour, it may be more desirable

to keep the traffic light running normally for as long as backup power is available. To address this issue, a new

feature called the Time of Day Action has been added to deactivate the timer during a user defined time period

up to twice each day.

Inverter

mode

entered

Dry contact activates

when enabled timer

counts down to zero

Timer starts to

count down

if enabled

Microprocessor

Real time clock

Peak period

settings

Disable Timer (Action=ON) or

Enable Timer (Action=OFF)

Figure 39 — Time Of Day Action Operation

You can define up to 2 peak time periods of the day:

1. Go to the UPS Maintenance > Relay & Load Shed screen.

2. In the Time of Day Action Configuration dialogue box, set up the start and end time of the first rush hour

under Time Period 1 and the second rush hour under Time Period 2. In this example, during the first time

period (7 AM to 9 AM), all 3 timers are disabled (they do not count down at all). Similarly, all timers are

disabled during the second time period (3 PM to 6 PM).

3. Select ON under each time period. Click the Update button under each time period to store the settings.

Confirm your settings in the UPS Monitoring > Relay & Load Shed > Time of Day Action Status screen.