017-237-B0 Rev A

34

Table D — Control Menu

LCD display

Meaning

Description

QUAL TIME

Line qualify time

Lets you set how long it takes for the Alpha Micro to return to Line mode after

the line has become requalified to make sure the line is stable. It can be set to 3, 

10, 20, 30, 40 or 50 seconds. The factory default setting is 3 seconds. Also See

“Adjusting and Controlling the Alpha Micro, #34: Line Qualify Time”.

BATT COMP

Battery

temperature

compensation

Lets you set the battery temperature compensation to match the batteries you are

using. It can be set to -2.5, -4, -5 or -6 mV/°C/Cell. The factory default setting is -5

mV/°C/Cell.

DATE FRMT

Date Format

Selection

This lets you toggle the Alpha FXM’s date format between YY-MM-DD, MM-DD-YY,

YYY-MM-DD, MM-DD-YYYY, DD-MM-YYYY, YY-TXT-DD, TXT-DD-YY, DD-TXT-YY,

YYYY-TXT-DD, TXT-DD-YYYY, DD-TXT-YYYY, YYYY-DD-TXT, YY-DD-TXT, YYYY-

DD-MM, YY-DD-MM. The factory default setting is MM-DD-YY.

CLOCK FRMT

Clock display

format option

Lets you select which format to display time information: in 24 hour clock format or

12 hour clock (AM/PM) format.

INV RECORD

Inverter record

clear

This clears the inverter counter and timer from the LCD’s system status menu. This

does not clear the 100-event log in the RS-232 menus.

CHGR CUR

Charger current

Allows you to set the battery charger current to either 0 A, 3 A, 6 A or 10 A. NOTE: If

you set the battery charger to 0 A, you will turn the charger off.

RELAY TEMP

Relay

temperature

Temperature setting to activate the specified dry contact. The configured dry contact 

will activate when the set battery temperature is reached. Setting range: 20ºC to

55ºC.

TEMP DISP

Temperature

display format

The temperature can be displayed in Celsius or Fahrenheit.

Daylight

Daylight saving

option

Switch "ON" this option to activate Day Light Saving time.