6.7.1 Wiring the RS-232 port

The Alpha Micro’s front panel has a DE-9 female connector. When connected to a PC with Windows HyperTer-

minal or other terminal emulation software, the Alpha Micro can be remotely monitored and controlled with it’s

command-line system. The Alpha UPS Monitor provides a Windows or web browser type of control.

Procedure

1. Connect a 9-pin, fully shielded, straight-through DE-9 to DE-9 connector cable between the computer’s port

and the Alpha Micro’s port.

2. Configure the communications parameters to the values shown in the terminal set up table below.

Figure 22 — RS-232 pin connections

Table F — Terminal Set Up Table

Emulation Type

VT 100 or

Compatible

Backspace

N/A

Duplex Mode

Half Duplex

Break Length

N/A

Xon/Xoff Flow Control

None

Emulation Type

N/A

RTS/CTS Flow Control

Off

Communication Parameters

Line Wrap

On

Handshaking

Software Handshaking

Screen Scroll

On

Baud Rate

2400 bps

CR Translation

CR

Data Format

8-bit Data, No Parity, 1 Stop Bit, No Flow Control.