Alpha Technologies Micro, Micro XL, Micro XL3 UPS User Manual

Page 91

Advertising
background image

89

017-237-B0 Rev A

Table W — Electrical Specifications

Parameter

Value

Input

Voltage (nominal), VAC

120 or 230 (optional 220).

Frequency, Hz, ±5%

60/50 (auto-frequency).

Current, Amps

(@ full load 10 A battery charger)

300: 5.4/3.0 @120/230 VAC

1000: 14/7.2 @120/230 VAC

Output

Voltage (nominal), VAC

120 or 230.

Frequency, Hz, ±5%

60/50 (auto-frequency).

Current, A

300: 2.5/1.3 @120/230 VAC

1000: 8.3/4.3 @120/230 VAC

Power, W/VA

300

1000

Waveform

Pure sine wave

Load Crest Factor

3:1 (load dependent)

Output Voltage Distortion

< 3% THD (resistive load)

Efficiency

Normal Mode

Backup (Inverter) Mode

> 92%, @ full load, 25°C.

> 72% (for 300), > 83% (for 1000) @ full load, 25°C.

Transfer Time, ms

AVR to Backup
Backup to AVR

5 (Typical)

5 (Typical)

Line Qualification Time, s

3 (factory default), user adjustable to 3, 10, 20, 30, 40, or 50.

Battery String Voltage

300: 24

1000: 48

Battery Charger Current, A

300: 3 *

1000: 10*

* User adjustable to 3, 6 or 10 A

Battery Charger Temperature

Compensation

-5 mV / °C / Cell (factory default), user adjustable to -2.5, -4, -5 or -6 mV / °C / Cell.

Battery size

Standard: 4 x 18 to 2 x 50 AHr

XL: 4 x 50 to 2 x 109 AHr

XL3: 8 x 50 to 4 x 109 AHr

Other

Fuse

5

(F1)

T4A 250 V for 24 V battery string voltage

T2A 250 V for 48 V battery string voltage