017-237-B0 Rev A

6.4 Operating the Alpha Micro

The control menu (Table D) lets you operate the Alpha Micro or program it to suit your operating conditions. You

can also use the Alpha UPS Monitor to make these adjustments. See “Alpha UPS Monitor”.

6.4.1 Procedure

1. From the Logo screen go to the Control menu.

2. Press the SELECT button to enter the submenu (Table D).

3. Press the SCROLL button to move between items in the submenu.

4. When you have reached the item you want to change, press the SELECT button. The item chosen is blinking.

5. To toggle between the choices, press the SCROLL button. Stop when you reach the choice you want.

6. To make the change, press the SELECT button. The blinking stops.

Table D — Control Menu

LCD display

Meaning

Description

INVERTER

Inverter

When inverter mode is set to ON, the Alpha Micro provides backup battery power

to the load. This mode of operation is normally activated automatically when line

power becomes unavailable, or the line power is not qualified. You can also put 

the Alpha Micro into this mode during initial startup in the absence of line power or

because of unqualified line power. See “Adjusting and Controlling the Alpha Micro, 

#31 Inverter On/Off”.

INV BYPASS

Inverter Bypass

This function can only be switched on when the Alpha Micro is in line mode. When

switched on, it locks the Alpha Micro into the Line mode, switched off the battery

charger and makes the output voltage equal to the input voltage. This is done to:

Replace the batteries.

OR:

Allow the use of a break-before-make manual bypass switch so the Alpha Micro can

be shut off for maintenance or replacement without interrupting power to the load.

BATT TEST

Battery Test

Lets you set the desired battery test duration to a value between 0 and 250 minutes.

Make sure that the set time duration is shorter than the depth of discharge of your

battery bank. Otherwise, you will drain the battery and trigger a fault. See "Batt Volt

low".

AUTO TEST

Automatic Test

If the GUI’s periodic self test is enabled, this starts the test no matter when it is

scheduled to take place.

SHUTDOWN

Shutdown

When this function is switched on, the Alpha Micro’s inverter is shut off. Neither Line

nor Inverter power is supplied to the load.

SENSE TYPE

Sense Type

This function can only be used when the Alpha Micro is in Standby or Shutdown

mode (Table C). This function toggles between:

NORMAL: The Alpha Micro can operate successfully with most line conditions.

OR:

GENERATOR: The Alpha Micro’s input voltage and frequency parameters are

expanded so the Alpha Micro can work with the fluctuations caused by a generator 

or noisy line.

FUNC MODE

Functional Mode

The Functional mode can only be changed when the Alpha Micro is in Standby

or Shutdown mode (Table C and Specifications, “Boost/Buck/Line Transfer 

Thresholds”). This function toggles between:

AUTOMATIC VOLTAGE REGULATION (AVR): The buck and boost modes are

active.

OR:

QUALITY: The buck and boost modes are switched off, the input voltage is the

Alpha Micro’s output voltage.

VOLTAGE

Voltage

Lets you set the Alpha Micro’s output voltage setting to 120 VAC, 230 VAC or

220 VAC. This should ONLY be done by a qualified technician acting under the 

instructions of Alpha Technologies Customer Service Department. Failure to contact

Alpha Technologies before performing this procedure could void your warranty.

FREQUENCY

Frequency

The frequency can only be changed when the Alpha Micro is in Standby mode.

This lets you set the Alpha Micro’s frequency setting to 50 Hz or 60 Hz. This should

ONLY be done by a qualified technician acting under the instructions of Alpha 

Technologies Customer Service Department. See "Service and Technical Support".

Failure to contact Alpha Technologies before doing this procedure could void your

warranty.