12. Emergency Shutdown Procedure
The Alpha Micro UPS contains more than one live circuit. In an emergency, line power may be disconnected at
the UPS’s input, but AC power can still be present at the output.
1. Switch OFF the input circuit
breaker.
2. Switch OFF the battery circuit
breaker.
3. Disconnect the AC input power.
4. Disconnect the battery string.
Input circuit breaker
Battery circuit breaker