background image

017-237-B0 Rev A

88

Table V — Mechanical Specifications

Parameter

Value

Dimensions H x W x D

mm (in)

Std: 19.7 (500) x 14.1 (358) x 11.6 (294).

XL: 30.6 (776) x 14.1 (358) x 11.6 (294).

XL3: 52.4 (1330) x 14.1 (358) x 11.6 (294).

Weight without batteries kg (lb)

Std: 43.4 (19.7).

XL: 49.8 (22.6).

XL3: 69.2 (31.4).

Color

White.

Mounting

Pole, wall, or pedestal with optional pedestal mounting kit.

Humidity

Operating: Non-condensing up to 95%.

Storage: Up to 95%.

Temperature

,

, °C

Operating

Storage

-40 to 50

1,2

.

-40 to 75

1,2

.

Altitude, m (ft)

Operating

Storage

Operating: Up to 3700

3

(12,000).

Storage: Up to 4600 (15,000).

AC input and output connectors

Terminal block, Wago p/n 862-0603 or equivalent (max 12 AWG)

Dry contact ATC connectors

Terminal block, mating plug JITE p/n PTB750B-03-1-03-3 or equivalent (max 16

AWG).

RS-232 connector

DE-9 Female.

Ethernet connector

Optional, factory installed RJ-45.

Dry contacts

6 sets of single-pole, double-throw relays located on the front panel. They are rated

at 250 VAC, 1A. The factory default settings are:

C1: On Battery.

C2, C3

5

: Low Battery.

C4: Load Shed Timer1.

C5: Alarm.

C6: 48/24 VDC for an external fan. It can be factory configured as a dry contact.

User inputs

Three optically-isolated and powered inputs are located on the front panel. When

they are shorted, their functions are:

S1: Starts the self test.

S2: Activates an alarm.

S3: Unit shutdown.

User interface

2 x 20 backlit alpha-numeric LCD screen

4

. Three control buttons located below.

Battery

Anderson Power mating part SB50 or equivalent.

9. Specifications

1. Above 50°C ambient, derate output power by 1.1% per °C rise, up to 74°C max.

2. Capable of operating at 100% of rated full load below 0°C down to -40°C after the Alpha Micro has been stabilized at 0°C for at least 1

hour.

3. Derate 2°C per 300 m (1000 ft) above 1400 m (4500 ft).

4. The LCD display may not function below -15°C. It gradually resumes normal operation as the temperature rises above -15°C. This will not

affect the operation of the Alpha Micro

5. CAUTION: Risk of electric shock and fire hazard, replace fuse with the same type and rating.