6.11.5 Types of Trigger

There are 3 types of trigger:

Edge trigger
When the user input changes from one state to the other, the Alpha Micro is triggered to perform Action #1. If the

level is set to High, the action will be triggered by a Low to High edge (leading edge). If the level is set to Low, the

action will be triggered by the High to Low edge (falling edge).

Figure 63 — Edge Trigger

Level Toggle
When the Level is set to High, the Alpha Micro is triggered to perform the other action when the user input chang-

es from Low to High. If the input then changes from High to Low, Action #2 will be triggered. In other words, a

level change in the user input will trigger an action toggle between Action #1 and #2.

Figure 64 — Level Trigger

Low to High

edge trigger

User input

Action #1

Action #1

(a) Level = High

User Input = Low to High, Action #1 is triggered
User Input = High to Low, no action triggered

High to Low

edge trigger

User input

Action #1

Action #1

(b) Level = Low

User Input = High to Low, Action #1 is triggered

User Input = Low to High, no action triggered

Action #1

Action #1

Action #2

Action #2

User input

(a) Level = High

User Input = Low to High, Action #1 is triggered

User Input = High to Low, Action #2 is triggered

Action #2

Action #2

Action #1

Action #1

User input

(b) Level = Low

User Input = High to Low, Action #1 is triggered

User Input = Low to High, Action #2 is triggered