6.2.1 SCTE-HMS Configurable Alarms, continued

Table 6-3, Recommended Settings for DSM3 Series Analog Alarms

Analog Alarms and Common Settings

Analog Alarms

Description

Alarm

Enable LOLO

LO

HI HIHI Deadband

psTotalStringVoltage

36V

Scaled representation of the full

battery string in 1/100 Volts units

0x0F

3300

3500

4520 4570 50

48V

0x0F

4400

4785

6030 6100 50

Individual Battery Voltage

Battery Voltage of 12V battery,

scaled 1/100 V

0x0F

1050

1150

1530 1550 20

psInputVoltage

120V

Scaled representation of the input

line voltage in 1/100 Volts units

0x0F

Varies by site. The XM2 will switch to standby at

nominal +15% -20%

220V

0x0F

psOutputVoltage

48V

Scaled representation of the

power supply output voltage in

1/100 Volts units.

0x0F

4300

4550

5050 5300 200

60V

0x0F

5650

6000

6600 7000 200

90V

0x0F

7800

8200

9150 9300 200

psPowerOut

Representation of power supply

output power in 1W units.

0x00

It is recommended that psOutputCurrent be used

for output alarms.

psStringChargeCurrent

Battery string charge current,

scaled in 1/100 Amp units.

0x0C

Disable Disable 1200 1250 20

psStringFloat

Battery string float charge current,

scaled in 1/100 Amp units.

0x0C

Disable Disable 1200 1250 20

psOutputCurrent

15A

Scaled representation of power

supply RMS current in 1/100 Amp

units.

0x0C

Disable Disable 1650 1720 20

18A

0x0C

Disable Disable 1980 2060 20

22A

0x0C

Disable Disable 2420 2530 40

24A

0x0C

Disable Disable 2640 2750 40

psTemperature

-40 to +80 degrees C

0x0F

Varies by site

docsIfDownChannelPower

The CM's receive RF power

scaled in 1/10 dBmV units

0x0F

-150

-10

10

150

15

docsIfCmStatusTxPower

The CM's transmit RF power

scaled in 1/10 dBmV units

0x0C

0

0

500

550

15

Alarms for Optional Generator

GenVBatIgnition

Scaled representation of the

generator's ignition battery in

1/100 Volts

0x0F

1150

1200

1500 1550 20

genEnclosureTemperature

Temperature inside generator's

enclosure in degrees C

0x09

-40

0

0

55

5

The following table displays the various analog alarms with common settings for the DSM3 Series

Communications Module.

6.0 Data Management

Analog Alarms and Common Settings, DPM

Analog Alarms

Description

Alarm

Enable LOLO

LO

HI HIHI Deadband

psInputVoltage

120V

Scaled representation of the input

line voltage in 1/100 Volts units

0x0F

Varies by site. The XM2-300HP will switch to

standby at nominal +10% -15%

220V

0x0F

psOutputVoltage

60V

Scaled representation of the

power supply output voltage in

1/100 Volts units.

0x0F

5150

5350

6150 6350 200

63V

0x0F

5650

6000

6600 7000 200

90V

0x0F

7800

8200

9150 9300 200

psOutputCurrent

3.5A

Scaled representation of power

supply RMS current in 1/100 Amp

units.

0x0C

Disable Disable 380

390

20

5.0A

0x0C

Disable Disable 550

575

20

The following table displays analog alarms with common settings for the DPM Communications

Module that differ from the DSM3 Series models.

Table 6-4, Recommended Settings for DPM Analog Alarms