0 alpha mib parameters, 1 definitions and settings, continued, Parameter oid description access type value – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual

Page 80

Advertising
background image

80

745-814-B8-001, Rev. C (03/2014)

10.1 Definitions and Settings, continued

Parameter

OID

Description

Access

Type

Value

COMMUNITY STRINGS

atiMgntSnmpCommunities

1.3.6.1.4.1.926.1.3.1.4.0

Object Identifier

atiMgmtSnmpCommGet

1.3.6.1.4.1.926.1.3.1.4.1.0

Default "Read" Community String

Read/Write

Octet String

AlphaGet (default

atiMgmtSnmpCommSet

1.3.6.1.4.1.926.1.3.1.4.2.0

Default "Read/Write" Community String

Read/Write

Octet String

AlphaSet (default)

SNMP TRAP

atiMgmtSnmpControls

1.3.6.1.4.1.926.1.3.1.5

Object Identifier

atiMgmtSnmpTrapOnNormal

1.3.6.1.4.1.926.1.3.1.5.1.0

Traps sent when an item in an alarm

state returns to normal.

Read/Write

Integer

1 = Disable
2 = Enable (Default)

atiMgmtSnmpSendCount

1.3.6.1.4.1.926.1.3.1.5.2.0

Number of times a trap is to be sent/

repeated.

Read/Write

Integer

1 to 9
1 (Default)

atiMgmtSysSnmpTimeout

1.3.6.1.4.1.926.1.3.1.5.3.0

The number of minutes allowed to pass

without SNMP communications. On the

lapse of this many minutes the device

will reset. Setting this value to zero will

prevent timeout resets.

Read/Write

Integer

0 to 65,000 (in minutes)
1440 (Default)

WEB SERVER ENABLE
atiMgmtSysHttpPrams

1.3.6.1.4.1.926.1.3.2.2.4

Object Identifier

atiMgmtSysHttpEnabled

1.3.6.1.4.1.926.1.3.2.2.4.1.0 Access to DSM3 via Web Browser

Read/Write

Integer

1=Disable
2=Enable (default)

SIMPLE NETWORK TIME PROTOCOL

atiMgmtSysServers

1.3.6.1.4.1.926.1.3.2.3.0

Object Identifier

atiMgmtSysServSntp

1.3.6.1.4.1.926.1.3.2.3.1.0

IP Address of SNTP Server (Optional)

Read/Write

IP Address

0.0.0.0 (Default)

ENVIRONMENTAL MANAGER

atiMgmtSysTempMgr

1.3.6.1.4.1.926.1.3.2.4.0

Object Identifier

atiMgmtSysTempCtrl

1.3.6.1.4.1.926.1.3.2.4.1.0

Environmental Control

Read/Write

Integer

1=off (Default)
2=OnTimer
3=OnTemp
4=onTimerTemp
5=on

atiMgmtSysTempStatus

1.3.6.1.4.1.926.1.3.2.4.2.0

Environmental Control Feedback State

Read Only

Integer

1=Contact Open (default)
2=Contact Closed

atiMgmtSysTempMode

1.3.6.1.4.1.926.1.3.2.4.3.0

Environmental Mode (Heat/Cool)

Read/Write

Integer

1=Heater (Default)
2=Cooler

atiMgmtSysTempActiveState

1.3.6.1.4.1.926.1.3.2.4.4.0

Environmental Control Contact State

(Open/Closed)

Read/Write

Integer

1=Closed (Default)
2=Open

atiMgmtSysTempTemperature

1.3.6.1.4.1.926.1.3.2.4.5.0

Environment Temperature

Read/Write

Integer

1..70ºC

atiMgmtSysTempHysteresis

1.3.6.1.4.1.926.1.3.2.4.6.0

Environmental Temperature Hysteresis

Read/Write

Integer

1..10ºC

atiMgmtSysTempTimer

1.3.6.1.4.1.926.1.3.2.4.7.0

Environmental Default Timer

Read/Write

Integer

0..1440 (30 Minute Default, 15

minute increments)

atiMgmtSysTempCountdown

1.3.6.1.4.1.926.1.3.2.4.8.0

Environmental Timer Time Remaining

Read Only

Integer

0..1440 (in minutes)

atiMgmtSysTempStatusInvert

1.3.6.1.4.1.926.1.3.2.4.9.0

State Inverted to match the type of relay

operation on the heater mat controller

Read/Write

Integer

1=No invert (Default)
2=Invert

PHONE HOME MANAGER
atiMgmtSysPhoneHomeIp

1.3.6.1.4.1.926.1.3.2.5

Object Identifier

atiMgmtSysPhoneHomeIp

1.3.6.1.4.1.926.1.3.2.5.1.0

Address for the Phone Home Frame

Read/Write

IP Address

0.0.0.0

atiMgmtSysPhoneHomeForce

1.3.6.1.4.1.926.1.3.2.5.2.0

Forces one Phone Home message

regardless of timers

Read/Write

Integer

1=No Operation (default)

2=Force

atiMgmtSysPhoneHomeTimer

1.3.6.1.4.1.926.1.3.2.5.3.0

Time since last frame transmitted, zero

means never transmitted

Read Only

Time Ticks

10.0 Alpha MIB Parameters