0 alpha mib parameters, continued, 1 definitions and settings, continued, Parameter oid description access type value – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual

Page 81

Advertising
background image

81

745-814-B8-001, Rev. C (03/2014)

10.1 Definitions and Settings, continued

Parameter

OID

Description

Access Type

Value

GENERAL CONTROLS

atiMgmtSysTamperPolarity

1.3.6.1.4.1.926.1.3.2.6.1.0

Determines when tamper is active

Read/Write

Integer

1=doorOpenWhenContactOpen
2=doorOpenWhenContactClosed
(default)

atiMgmtSysAlphaBusSize

1.3.6.1.4.1.926.1.3.2.6.2.0

Internal microprocessor communications bus size.

Alpha XM2 series power supplies use 9 bit. Alpha

GMX and VMX series supplies use 8 bit

Read/Write

Integer

1=9 Bit (Default)
2=8 Bit

atiMgmtSysGnrlInfoConfigs

1.3.6.1.4.1.926.1.3.2.7.1

Object Identifier

atiMgmtSysGnrlInfoConfigsMain

1.3.6.1.4.1.926.1.3.2.7.1.1.0

An ASCII string programmed into the main board

non-volatile memory.

Read Only

Octet String

Product number, configuration

number serial number, etc.

atiMgmtSysGnrlInfoConfigsDaughter

1.3.6.1.4.1.926.1.3.2.7.1.2.0

An ASCII string programmed into the C/D battery

circuitry (DSM3x only).

Read Only

Octet String

Product number, configuration

number serial number, etc.

atiMgmtSysGnrlInfoConfigsBase

1.3.6.1.4.1.926.1.3.2.7.1.3.0

An ASCII string describing the base configuration

of the device.

Read Only

Octet String

i.e. DSM3, DSM3x, DPM, etc.

ENVIRONMENTAL I/O CONTROLLER

atiMgmtSysIo

1.3.6.1.4.1.926.1.3.2.8

Object Identifier

atiMgmtSysIoSelect

1.3.6.1.4.1.926.1.3.2.8.1

Indicates what function the IO pins are being

used for

Read/Write

Integer

1 = Generic

2 = lapOnly

3 = heaterControlOnly

4 = generatorOnly

5 = heaterControlAndLap

6 = generatorAndLap

atiMgmtSysIoLAPState

1.3.6.1.4.1.926.1.3.2.8.2

Current state of the LAP device

Read Only

Integer

1: notInstalled(1)

2: ok(2)

3: acNotPresent(3)

4: lapBlown(4)

5: lapFail(5)

atiMgmtSysIoGenState

1.3.6.1.4.1.926.1.3.2.8.3

State of the DC Emergency Generator when

sense lines are used

Read Only

Integer

1: notInstalled(1)

2: genOff(2)

3: genRunning(3)

4: genNotDetected(4)

5: error(5)

atiMgmtSysIoPinCtrl

1.3.6.1.4.1.926.1.3.2.8.20

Status of the ENV connector Output Pin (Pin 3)

Read Only

Integer

1 = Contact Open

2 = Contact Closed

atiMgmtSysIoPinIn4

1.3.6.1.4.1.926.1.3.2.8.21

Status of the ENV connector Input Pin#4

Read Only

Integer

1 = Contact Open

2 = Contact Closed

atiMgmtSysIoPinIn5

1.3.6.1.4.1.926.1.3.2.8.22

Status of the ENV connector Input Pin#5

Read Only

Integer

1 = Contact Open

2 = Contact Closed

atiMgmtSysIoPinIn6

1.3.6.1.4.1.926.1.3.2.8.23

Status of the ENV connector Input Pin#6

Read Only

Integer

1 = Contact Open

2 = Contact Closed

PLATFORMS
atiProductPlatforms

1.3.6.1.4.1.926.1.4

Object Identifier

atiBroadbandUPS

1.3.6.1.4.1.926.1.4.1

Object Identifier

atiBBSysView

1.3.6.1.4.1.926.1.4.1.1

Object Identifier

atiBBSysViewSelects

1.3.6.1.4.1.926.1.4.1.1.1

Object Identifier

atiBBSysViewSelfTestControl

1.3.6.1.4.1.926.1.4.1.1.1.1.0

Starts/Stops a system self-test.

Read/Write

Integer

1=Stop
2=Start

atiBBSysViewSelfTestInhibit

1.3.6.1.4.1.926.1.4.1.1.1.2.0

System self-test is prevented. On reset, the DSM

gets this value from the master XM2 (in a system

with more than one power supply).

Read/Write

Integer

1=Normal (Default)
2=Inhibited

atiBBSysViewSystemControlMgr

1.3.6.1.4.1.926.1.4.1.1.1.3.0

If the System Control Manager is running, the

Small System Controller/Administrator (SSC or

SSA) is running and there is coordination between

the power supplies for charging, testing, etc. The

value of this item is stored in non-volatile memory.

Read/Write

Integer

1=Running
2=Disabled

10.0 Alpha MIB Parameters, continued