0 alpha mib parameters, continued, 1 definitions and settings, continued, Parameter oid description access type value – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual

Page 82

Advertising
background image

82

745-814-B8-001, Rev. C (03/2014)

Parameter

OID

Description

Access Type

Value

SYSTEM ALARMS
atiBBSysViewAlarms

1.3.6.1.4.1.926.1.4.1.1.2

Object Identifier

atiBBSysViewMajorAlarm

1.3.6.1.4.1.926.1.4.1.1.2.1.0

Indicates if any of the items monitored are in a major

alarm state.

Read Only

Integer

1=OK

2=Alarm

atiBBSysViewMinorAlarm

1.3.6.1.4.1.926.1.4.1.1.2.2.0

Indicates if any of the items monitored are in a minor

alarm state.

Read Only

Integer

1=OK

2=Alarm

atiBBSysViewSelfTestResult

1.3.6.1.4.1.926.1.4.1.1.2.3.0

If any of the items being monitored indicate that

self-test failed, this item indicates a failure.

Read Only

Integer

1=OK

2=Fail

atiBBSysViewTempProbeStatus

1.3.6.1.4.1.926.1.4.1.1.2.4.0

If any of the devices being monitored indicate a

temp probe failure or absence, this item will alarm.

Read Only

Integer

1=OK

2=Missing

atiBBSysViewInputStatus

1.3.6.1.4.1.926.1.4.1.1.2.5.0

If ALL the items being monitored indicate no AC, this

item will alarm.

Read Only

Integer

1=OK

2=No AC Present

SCALARS
atiBBSysViewScalars

1.3.6.1.4.1.926.1.4.1.1.3

Object Identifier

atiBBSysViewInputVoltage

1.3.6.1.4.1.926.1.4.1.1.3.1.0

Power supply input voltage.

Read Only

Integer

atiBBSysViewInputFrequency

1.3.6.1.4.1.926.1.4.1.1.3.2.0

Power supply input line frequency.

Read Only

Integer

atiBBSysViewInputCurrent

1.3.6.1.4.1.926.1.4.1.1.3.3.0

Power supply input current.

Read Only

Integer

atiBBSysViewBatteryVoltage

1.3.6.1.4.1.926.1.4.1.1.3.4.0

Battery voltage.

Read Only

Integer

atiBBSysViewBatteryTemperature

1.3.6.1.4.1.926.1.4.1.1.3.5.0

Battery temperature (Degrees C).

Read Only

Integer

atiBBSysViewChargerCurrent

1.3.6.1.4.1.926.1.4.1.1.3.6.0

Sum of charging current from all power supplies.

Read Only

Integer

atiBBSysViewChargerVoltsFloat

1.3.6.1.4.1.926.1.4.1.1.3.7.0

Battery charger float voltage.

Read/Write

Integer

atiBBSysViewChargerVoltsEqualize

1.3.6.1.4.1.926.1.4.1.1.3.8.0

Battery charger equalization voltage.

Read/Write

Integer

atiBBSysViewChargerVoltsTemperatureComp 1.3.6.1.4.1.926.1.4.1.1.3.9.0

Battery charger temperature compensation
(0 to 5mV/Cell/°C).

Read/Write

Integer

atiBBSysViewBatteryCapacity

1.3.6.1.4.1.926.1.4.1.1.3.10.0

Battery string capacity (Amp hours).

Read/Write

Integer

SCALARS
atiBBSysViewCounters

1.3.6.1.4.1.926.1.4.1.1.4

Object Identifier

atiBBSysViewSelfTestInterval

1.3.6.1.4.1.926.1.4.1.1.4.1

Number of days between automated self tests

Read-Write

Integer

0..65535

atiBBSysViewSelfTestCountdown

1.3.6.1.4.1.926.1.4.1.1.4.2

Number of days until the next automated self test

Read-Write

Integer

0..65535

atiBBSysViewSelfTestDuration

1.3.6.1.4.1.926.1.4.1.1.4.3

Number of minutes for which an automated self

test will run

Read-Write

Integer

0..65535

atiBBSysViewInverterRuntime

1.3.6.1.4.1.926.1.4.1.1.4.4

Number of minutes the inverter has run due to an

AC fail event

Read Only

Integer

0..65535

atiBBSysViewStandbyEvents

1.3.6.1.4.1.926.1.4.1.1.4.5

Number of times the inverter has gone into standby

due to an AC fail event

Read Only

Integer

0..65535

atiBBSysViewRuntimeRemaining

1.3.6.1.4.1.926.1.4.1.1.4.6

Seconds of estimated runtime remaining when in

standby

Read Only

Integer

0..65535

atiBBSysViewTimeInStandby

1.3.6.1.4.1.926.1.4.1.1.4.7

Seconds. If currently in standby, time in standby. If

not in standby this value will be zero

Read Only

Integer

0..-1

atiBBSysViewTimeSinceLastStandby

1.3.6.1.4.1.926.1.4.1.1.4.8

Seconds. The accumulated time since the end of

last standby event and the start of the next standby

event. The counter will reset to zero after the next

standby event has ended.

Read Only

Integer

0..-1

atiBBSysViewTimeInLastStandby

1.3.6.1.4.1.926.1.4.1.1.4.9

Seconds. The length (time) of last standby event.

If currently in a standby event this value will be the

length of the previous standby event. This value will

be updated at the conclusion of each standby event.

This item is saved in non-vol memory.

Read Only

Integer

0..-1

DETECT 6V BATTS
atiCibDiscTable

1.3.6.1.4.1.926.1.2.1.1.1.5.14.0.11 Controls the ability to detect and report 6 Volt

batteries.

Read/Write

Integer

0 = default

1 = Detect 6 Volt

Batteries

10.1 Definitions and Settings, continued

10.0 Alpha MIB Parameters, continued