7.0 Installation

7.9.11 Connecting the Battery Heater Mat Controller

Power to the heater mat is provided via a customer-supplied controller plugged into the power

outlet inside the enclosure. A cable (Alpha p/n 875-627-22) connects the controller to the ENV

(Environmental) connector on the DSM3x and DPM. The connection procedure is shown below.

1. Connect the 4-pin connector

from the controller cable (Alpha

p/n 875-627-22) into the base of

the Heater Mat Controller.

2. Plug the controller into

the power outlet.

4. Plug the 6-pin connector

into the ENV connector.

3. Plug the Heater Mat into the controller.

7.9.10 I/O Port: Heater Mat Control

atiMgmtSysIoSelect = 3,5

A battery heater mat controller may be managed though the following set of parameters within the

‘atiMgmtSysTempMgr’ MIB branch.

Parameter

Access Values

Description

atiMgmtSysTempCtrl

1.3.6.1.4.1.926.1.3.2.4.1.0

RW

1 = Off 2 = Switch on Timer Starts or stops the heater mat

activation timer

atiMgmtSysTempStatus

1.3.6.1.4.1.926.1.3.2.4.2.0

R

1 = Contact Open 2 =

Contact Closed

The heater mat is activated when this

parameter reports “2”

atiMgmtSysTempTimer

1.3.6.1.4.1.926.1.3.2.4.7.0

RW

0..1440 (Default = 30)

The number of minutes the heater mat

will stay on when timer is started

atiMgmtSysTempCountdown

1.3.6.1.4.1.926.1.3.2.4.8.0

R

0..1440

Number of minutes remaining on timer

atiMgmtSysTempStatusInvert

1.3.6.1.4.1.926.1.3.2.4.9.0

RW

1 = No invert (default) 2 -

Invert

The manufacturer of the mat control

block created some models where the

polarity is reversed (Open vs closed).

If these devices are deployed then this

parameter will need to be set to “2”

Table 7-6, I/O Port: Heater Mat Control Specifications

Heater control MIBs will continue to report regardless of atiMgmtSysIoSelect value, but DSM3x/DPM Web page will

only display Heater Control status if atiMgmtSysIoSelect is set to “3” or “5.”

NOTE: