Table 7-1, tamper (tpr) switch specifications, 9 i/o connections (tpr, env), 1 tamper (tpr) switch interface – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual

Page 64: 0 installation

Advertising
background image

64

745-814-B8-001, Rev. C (03/2014)

7.0 Installation

7.9

I/O Connections (TPR, ENV)

The Alpha DSM3 series transponders (DSM3, DSM3x, DPM) are all populated with a Tamper interface to

report the status of the power supply enclosure door when equipped with the optional tamper switch. The

Alpha DSM3x and DPM are populated with the Environmental and I/O Controller interface (referred to in

this section as I/O Port) which can be used to monitor and control an array of contact relay devices such

as battery heater mats, enclosure moisture sensors and emergency generators.

7.9.1 Tamper (TPR) Switch Interface

The tamper switch interface is designed to report and alarm the status of the power supply

enclosure door. The circuit created by the tamper switch is a contact relay, so other contact relay

devices can be designed to be monitored through this interface. For example, the Alpha Utility

Line Sensor (Alpha P/N 746-399-20) uses the tamper interface to monitor the Utility outlet to

report the presence of line voltage.

Fig. 7-18, I/O (ENV) and Tamper Switch Interface (TPR) Connection Locations

I/O Control Interface (ENV)

Tamper Switch Interface (TPR)

Table 7-1, Tamper (TPR) Switch Specifications

Function

Parameter

OID

Values

Description

Tamper

psTamper

1.3.6.1.4.1.5591.1.4.2.1.27.X

See Note 1

1 = Closed

2 = Open

Status of enclosure

door

Utility

Sense

psTamper

1.3.6.1.4.1.5591.1.4.2.1.27.X

1 = No Voltage

2 = Voltage present

Status of Utility

Voltage

tamperPolarity

1.3.6.1.4.1.926.1.3.2.6.1.0

1 = Report “Open” when

contact open

2 = Report “Open” when

contact closed

Controls polarity of

‘psTamper’ reporting

Alarm/

Trap

psTamper(Closed) 1.3.6.1.4.1.5591.1.1.3.1.3.13.1

.3.6.1.4.1.5591.1.4.2.1.27.X.1

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable for

psTamper=”Closed”

Alarm/

Trap

psTamper(Open)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1

.3.6.1.4.1.5591.1.4.2.1.27.X.2

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable for

psTamper=”Open”

In the OID column of the following table, ‘X’ denotes power supply device address (Default = 1)

NOTE:

Advertising