7.0 Installation

atiMgmtSysIoSelect (1.3.6.1.4.1.926.1.3.2.8.1.0)

MIB Value

Device

Reported Parameter or MIB Branch

1

No device (generic)

I/O Pins Only

2

LAP Only

atiMgmtSysIoLAPState 1.3.6.1.4.1.926.1.3.2.8.2.0

3

Heater Control Only

atiMgmtSysTempMgr * 1.3.6.1.4.1.926.1.3.2.4

4

DC Generator Only

atiMgmtSysIoGenState 1.3.6.1.4.1.926.1.3.2.8.3.0

5

Heater Control and LAP

atiMgmtSysIoLAPState atiMgmtSysTempMgr *

6

Generator and LAP

atiMgmtSysIoLAPState atiMgmtSysIoGenState

*MIBs within atiMgmtSysTempMgr branch will report and control will be allowed regardless of

the value reported by atiMgmtSysIoSelect

Table 7-3, I/O Port Specifications

Function Parameter

OID

Values

Description

Input

atiMgmtSysIOPinIn4 1.3.6.1.4.1.926.1.3.2.8.21.0

1 = Contact Open

Input

atiMgmtSysIOPinIn5 1.3.6.1.4.1.926.1.3.2.8.22.0

1 = Contact Open

2 = Contact Closed

Used to monitor

moisture sensor

Input

atiMgmtSysIOPinIn6 1.3.6.1.4.1.926.1.3.2.8.23.0

1 = Contact Open

2 = Contact Closed

Control

atiMgmtSysIOPinCtrl 1.3.6.1.4.1.926.1.3.2.8.20.0

1 = Contact Open

2 = Contact Closed

Open/Close a

contact

Alarm/

Trap

IOPinIn4(Open)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.21.0.1

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

Pin4 contact is Open

Alarm/

Trap

IOPinIn4 (Closed)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.21.0.2

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

Pin4 contact is

Closed

Alarm/

Trap

IOPinIn5 (Open)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.22.0.1

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

Pin5 contact is Open

Alarm/

Trap

IOPinIn5 (Closed)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.22.0.2

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

Pin5 contact is

Closed

Alarm/

Trap

IOPinIn6 (Open)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.23.0.1

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

Pin6 contact is Open

Alarm/

Trap

IOPinIn6 (Closed)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.23.0.2

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

Pin6 contact is

Closed

Alarm/

Trap

IOPinCtrl (Open)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6.

1.4.1.926.1.3.2.8.20.0.1

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

control contact is

Open

Alarm/

Trap

IOPinCtrl (Closed)

1.3.6.1.4.1.5591.1.1.3.1.3.13.1.3.6

.1.4.1.926.1.3.2.8.20.0.2

1 = disable

2 = enableMajor

3 = enableMinor

Alarm enable when

control contact is

Closed

7.9.4 I/O Port: Generic Device

The I/O connector on the Alpha DSM3x and DPM allow the headend to remotely monitor and

control external contact relay devices. Each input pin can be configured through the SCTE-HMS

discretePropertyTable for alarm and SNMP trap generation.

Table 7-4, I/O Port: Generic Device Specifications

7.9.3 Configuring I/O Port Connections, continued