0 specifications – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual

Page 84

Advertising
background image

84

745-814-B8-001, Rev. C (03/2014)

11.0 Specifications

Specifications for AlphaNet DSM3 Family

DSM3x

DSM3

DPM

Power Supply Models Supported: XM2-HP, XM2, GMX, VMX

XM2-HP, XM2, GMX, VMX

XM2-300HP

Battery Monitoring:

Up to four strings of 36 or 48V

batteries (6V batts configurable up to

two strings)

Up to two strings of 36 or 48V

batteries (6V batts configurable

up to two strings)

One 12V battery (or two if

AlphaCells

Power System Management:

Up to five power supplies and an

AlphaGen generator are managed

from a single DSM3 Series including

coordinated battery charging, system

test and aggregated alarms

N/A

N/A

Management Protocol:

Standard ANSI/SCTE-HMS MIBs support basic power supply monitoring. Advanced diagnostics with

battery and power module analytics available via secure SNMP

Advanced Diagnostics

1

Intelligent Power Supply

Interface:

Power supply user interface displays advanced diagnostics including: DOCSIS modem upstream and

downstream RF levels, IP address assigned by network DHCP server, MAC address and firmware levels,

including battery voltages to verify correct wire harness installation

Hardware

RF Cable Interface:

F-connector, female, 75 Ohm, connector angle better accommodates coax bend radius when installed in

some enclosures

Local Interface:

RJ-45, Ethernet, 10/100

LED Indicators:

Ready/Alarm, Upstream registration, Downstream lock, AlphaBus activity, RF level, Link, CPE traffic, Battery

Sense harness correctly connected

I/O Control (DSM3x Series and

DPM Only):

6-pin Molex: Digital input, Digital output, 5V, Common

AlphaBus:

RJ-11 offset tab: Multiple-power supply and AlphaGen communications

Battery Monitoring:

8-pin Molex battery string A/B and

8-pin Molex battery string C/D.

8-pin Molex battery string A/B

N/A

Tamper:

NO or NC, software configurable, reads enclosure door magnetic switch

Environment

Operating Temperature:

-40 to 65°C / -40 to 149°F

Storage Temperature:

-40 to 85°C / -40 to 185°F

Humidity:

10 to 90% non-condensing

Regulatory Compliance:

FCC Part 15 Class A

EN 50083-2:2006 EMC requirements for CATV equipment

EN 62040-2:2006 Uninterruptable power supply EMC requirements, Category C2

Surge: IEEE 587, Category B3

RoHS: Directive 2002/95/EC

1

Advanced diagnostics are available through Alpha Certified network monitoring systems

Network Communications

DOCSIS (RF) Port Protocols:

IP, UDP, TCP, DHCP, TFTP, SNMPv1,SNMPv2c, HTTP, SNTP

Ethernet Port:

Local Mode: HTTP Web interface for local on-site diagnosis.

CPE Mode: DOCSIS Cable modem Ethernet CPE functionality

MIBs:

Power supply (ANSI/SCTE 38-4)

Other SCTE-HMS MIBs as defined by the SCTE for power supply and generator status monitoring

Alpha proprietary advanced UPS diagnostics