7.0 Installation

Once the connection has been made, Environmental Control Management can be configured

using an SNMP MIB browser as indicated in the following tables. The Environmental Control MIB

section begins at atiMgmtSysTempMgr (1.3.6.1.4.1.926.1.3.2.4). Status of the Environmental

Control is also available via the Communications Module’s Web page by navigating to ‘Advanced

Configuration’, ‘I/O – Environment’. Ensure the ‘Heater/Cooler Only’ is selected from the drop-

down list.

Set these OIDs to the specified value

Functionality

atiMgmtSysTempTemperature (1.3.6.1.4.1.926.1.3.2.4.5) to 5

Heater turns on at 5°C

atiMgmtSysTempHysteresis (1.3.6.1.4.1.926.1.3.2.4.6) to 3

3°C of permitted controller overshoot (in this case, would turn off at 8°C)

atiMgmtSysTempCtrl (1.3.6.1.4.1.926.1.3.2.4.1) to 3

Battery temperature sensor used to control heater setpoint

atiMgmtSysTempMode (1.3.6.1.4.1.926.1.3.2.4.3) to 1

Places controller in heater mode

atiMgmtSysTempActiveState (1.3.6.1.4.1.926.1.3.2.4.4) to 1

Drive pin to the temperature device will go low when heater is on

atiMgmtSysTempStatusInvert (1.3.6.1.4.1.926.1.3.2.4.9) to 1

Sets the polarity of the feedback signal from the temperature device

During operation, the following MIB points will report the current temperature and whether the

heater is on or off.

SNMP MIB Point

Data

atiMgmtSysTempStatus (1.3.6.1.4.1.926.1.3.2.4.2)

Temperature device ON or OFF

atiBBSysViewBatteryTemperature (1.3.6.1.4.1.926.1.4.1.1.3.5)

Battery temperature (in degrees C)

7.9.12 Configuring the Battery Heater Mat Controller

In this example, values are written to their respective OIDs to set temperatures, control mode and

status reporting.

Table 7-7, Heater Mat OIDs and Functionality

Table 7-8, Heater Mat MIB Reports

7.9.11 Connecting the Battery Heater Mat Controller, continued