Technical data, Visual representation – Burkert Type 1150 User Manual

Page 13

Advertising
background image

1150 - 11

S

YSTEM

DESCRIPTION

Visual Representation

Technical data

Thermocouple input

Input for resistance thermometer (RTD)

Designation

Measurement range

Meas. accuracy

1

Ambient
temperature
error

Fe-CuNi "L"
Fe-CuNi "J"

Cu-CuNi "U"
Cu-CuNi "T"

NiCr-Ni "K"
NiCr-CuNi "E"
NiCrSi-NiSi "N"
Pt10Rh-Pt "S"
Pt13Rh-Pt "R"
Pt30Rh-Pt6Rh "B"

W5Re-W26Re "C"
W3Re-W25Re "D"
W3Re-W26Re

DIN EN 60584

DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584

-200 to +900°C
-200 to +1200°C
-200 to +600°C
-200 to +400°C
-200 to +1372°C
-200 to +1000°C
-200 to +1300°C

0 to 1768°C
0 to 1768°C
0 to 1820°C
0 to 2320 °C
0 to 2495 °C
0 to 2400 °C

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

0.25%

100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K

Cold junction

Pt 100 internal, external or constant

1

With 250 msec sampling time.

Designation

Connection
circuit

Measurement
range

Meas. accuracy

1

Ambient
temperature
error

Pt100

DIN EN 60751

2-wire/3-wire

-200 to +850°C

0.05%

50 ppm/K

Pt 50,500, 1000

DIN EN 60751

2-wire/3-wire

-200 to +850°C

0.1%

50 ppm/K

Cu50

2-wire/3-wire

-50 to +200°C

0.1%

50 ppm/K

Ni100

DIN 43 760

2-wire/3-wire

-60 to +250°C

0.05%

50 ppm/K

KTY11-6

2-wire

-50 to +150°C

1.0%

50 ppm/K

PtK9

2-wire

lithium-chloride transducer

Sensor lead resistance

max. 30 ohms per lead for 2-wire or 3-wire circuit

Meas. current

250

A

Lead compensation

is not required for 3-wire circuit. With a 2-wire circuit, the lead resistance can be

compensated in software by a correction of the process value.

1

With 250 msec sampling time.