C

ONFIGURATION

Ratio control

Control is always based on variable a.

The math module forms the ratio of the measurements of a and b (a/b) and produces the setpoint for the
controller. The ratio is made available as a value, via the function “Math X”, and can be displayed.

The required ratio a/b is programmed as the setpoint (ratio setpoint) in the setpoint definition.

Humidity control

The humidity controller receives the process value from a psychrometric humidity probe, through the
mathematical combination of wet bulb and dry bulb temperatures.

Variable a - dry temperature
Variable b - wet temperature

The math and logic module can be enabled through the code or the setup program.

Extras Enable device options

Enabling the math and logic module