Controller 1 (2 to 4) / Configuration

The setpoint limits are not effective if the setpoint is set by the pc via the interface.

In case of correction of an external setpoint the limitation is valid for the sum of both
(setpoint + correction).

Value / selection

Description

Dead band

0 to 100

The output movement is suppressed within the dead band;
e.g. with noisy signals.

The dead band is only effective for controller structures with an I-component.

External setpoint

without correction
with correction

External setpoint input without correction
External setpoint input with correction

External setpoint with correction:
External setpoint + seponit 1 = present setpoint

The external setpoint is corrected up or down from the keypad (setpoint 1). The
display shows the present setpoint.

Activating the function:

Controller 1 / Inputs / External setpoint

Setpoint

Start value
- 1999 to 0 to + 9999

Setpoint limiting prevents the input of values outside the defined range.

End value

- 1999 to 400 to + 9999

Output level

Start value
- 1999 to 0 to + 9999

Output standardization for cascade control:

If the controller channel serves as a master controller, then the controller output

signal (output 0 to 100 %) must be scaled to match the setpoint range of the
slave controller.

End value

- 1999 to 100 to + 9999

Cascade controller

No function
Master controller 1
Slave controller 1
Master controller 2
Slave controller 2

Activates cascade control and defines the control channel as a master or slave
controller for cascade 1 or 2.

NOTE