Burkert Type 1150 User Manual

Page 70

Advertising
background image

68 - 1150

C

ONFIGURATION

Zero point resp. end value - Example: Setting with controller outputs for cooling.
The following settings have to be defined for double-setpoint controllers:
Zero point: 0 / End value: -100

NOTE

Analog outputs / Analog output 1 (2 to 6) / ...

Logic outputs / Logic output 1 (2 to 12) / ...

Value / selection

Description

Function

(Binary selector)
Outp. 1 contr. 1

Factory-set for logic output 2 to 12: Switched off

Output mode

none

Time delay

Pulse

Time delay:
The switch-on / switch-off edges can be delayed by a definable time period.

Pulse:

A definable pulse / pause ratio can be applied to the output.

ON time

- 1999 to 0 to + 9999

Delay of switch-on edge or pulse time.

OFF time

- 1999 to 0 to + 9999

Delay of switch-off edge or pulse time.

Value / selection

Description

Zero point

- 1999 to 0 to + 9999

A physical output signal is assigned to the value range of a output variable.

Example:
Setpoint 1 (value range: 150 to 500°C) is to be output via the analog output
(0 to 20 mA).
i.e.: 150 to 500 °C = 0 to 20 mA

Zero point: 150 / End value: 500

End value

- 1999 to 100 to + 9999

A physical output signal is assigned to the value range of a output variable.

Example:

see above "Zero point"

Offset

- 1999 to 0 to + 9999

Value of the parallel shift applied to the analog output values.