Controller, Controller 1 (2 to 4) / configuration – Burkert Type 1150 User Manual

Page 58

Advertising
background image

56 - 1150

C

ONFIGURATION

Controller

The following are set here: controller type, input variables of the controller, the
setpoint limits, conditions for manual mode and the presettings for selfoptimization
of the four controller channels.

Value / selection

Description

Controller type

2 point process controller
3 point process controller
3 point step

Position control

Continuous

2 point process controller
3 point process controller
3 point step automatic controller
Continuous automatic controller with integrated position control
Continuous automatic controller

Control action

Direct
Inverse

Direct:

The controller output Y is > 0 when the process value is smaller than the setpoint

(e.g. cooling).
Inverse:

The controller output Y is > 0 when the process value is larger than the setpoint

(e.g. heating).

Inhibit manual mode

Free
Inhibited

If the manual mode is inhibited, changing over to "manual" is not possible from

the keys or via the logic input.

Manual output

- 100 to 101

Defines the output after changing over to manual mode.
101 = last output

Range output

- 100 to 0 to 101

Output on out-of-range.

101 = last output

Controller 1 (2 to 4) / Configuration