36 - 1150

O

PERATION

AND

C

ONTROLLER

FUNCTIONS

Operating „program controller/generator“

Program editor

50 programs with up to 99 segments can be programmed; a total of 1000 segments can be implemented.

Programs are created by programming setpoints and segment times, segment by segment.

Furthermore, the states of the control contacts 1 — 8 and the active parameter set can be defined for
each segment.

The setpoint profiles can be output either as a ramp or a step (configurable).

Output as a ramp has been chosen for the following diagrams.

If the instrument is configured as a program controller/generator, programs have to be created first, by
using the internal program editor or the setup program.

General

To monitor the process value, a tolerance band can be applied around the setpoint profile for each
segment.

If the upper or lower limit is infringed, a tolerance band signal is generated, which is internally processed
or produced via an output.

(see Chapter

“Outputs and Logic functions“)

Tolerance band