Equipotentiality of the installation – Burkert Type 8076 User Manual

Page 30

Advertising
background image

28

Installationandwiring

5,5

11,5

20

5,5

11

5

20

5

Strip 20 mm of the cable.

Cut the central wire (earth) so that its length is equal to 11.5 mm.

Expose 5.5 mm of the wires on the stripped cable.

Insert each wire into the appropriate pin on the terminal block [5] (see chap. 8.3.4
to chap. 8.3.6).

Tighten the terminal block [5] wired to the body [4].

Tighten the connector nut [1].

Figure 16 :

Multipin M12 connector (available as an accessory)

8.3.3.

equipotentiality of the installation

To ensure the equipotentiality of the installation (power supply - device - fluid):

Connect together the various earth spots in the installation to eliminate the potential differences that may
occur between different earthes.

Observe faultless grounding of the shield of the power supply cable.

Special attention has to be paid if the device is installed on plastic pipes because there is no direct earthing
possible. Proper earthing is performed by earthing together the metallic devices such as pumps or valves, that
are as close as possible to the device.

Power supply

12-36 V DC

+

-

Figure 17 :

Equipotentiality skeleton diagram with pipes in metal

Power supply

Devices such as valves,
pumps,..

Pipes in plastic

12-36 V DC

+

-

Figure 18 :

Equipotentiality skeleton diagram with pipes in plastic

English

Type 8026- 8036- 8076

Advertising
This manual is related to the following products: