60

Adjustmentandcommissioning

9.14. Diagnostic menu

9.14.1. modifying the Diagnostic menu access code

See chap. 9.10 to access the Diagnostic menu. The default access code is "0000".

Enter the new
access code to the
DIAGNOSTIC menu

Confirm the new
code

Code

System

Diagnostic

0***

Confirm

0***

9.14.2. monitoring the sensor input frequency

See chap. 9.10 to access the Diagnostic menu.

A malfunction in your process or the sensor may be revealed by an out-of-range input frequency.

The function allows for monitoring the sensor input frequency and configure the behaviour of the device if the
parametered ranges are exceeded.

The sensor input frequency f is used to determine the flow Q in the pipes using the formula f = KQ (the K factor
being expressed in pulses/s and the flow rate Q in l/s).

To be warned when the input frequency is out of range:

activate monitoring of the sensor input frequency in the function "activate", then

enter an input frequency range outside of which the device generates a “warning” event and displays the icons

and

.

enter an input frequency range outside of which the device generates an “error” event and displays the icons

and

ERR

.

Frequency

Sensor

Activate

Frequency

Warn Hi

Warn Lo

Err Hi

Err Lo

Diagnostic

INPUT

INPUT

INPUT

INPUT

READ

ACTIVATE: choose whether or not to activate monitoring of the sensor input frequency.
This monitoring is done by the generation of a “warning” event if the input frequency range defined in the “Warn
hi/lo” functions below is exceeded and an “error” event if the input frequency range defined in the “Err hi/lo” func-
tions below is exceeded.
FREQUENCY: read the sensor input frequency
WARN HI: enter the input frequency value above which a "warning" event is generated.
WARN LO: enter the input frequency value below which a "warning" event is generated.
ERR HI: enter the input frequency value above which an "error" event is generated.
ERR LO: enter the input frequency value below which an "error" event is generated.