9.13.3. resetting totalizer 1 or totalizer 2 respectively

See chap. 9.10 to access the Calib menu.

System

Calib

Total 1

Reset Yes/No

Total 2

Reset Yes/No

TOTAL 1 or TOTAL 2 respectively: Reset (choice “Yes”) or do not reset (choice “No”) totalizer 1 or totalizer 2
respectively.

Totalizer 2 can be reset from Process level. See chap. 9.9.

9.13.4. Adjusting the current outputs

Warning

risk of injury due to wrong adjustment.
• Make sure the Hold mode is disabled (see chap. 9.13.1).

See chap. 9.10 to access the Calib menu.

Outputs

Calib

AC1 / AC2

4mA:

INPUT

20mA:

INPUT

The entered values are not memorised in this menu. Only the values emitted on the current outputs are
adjusted after pressing “OK” when the message “Recalibrate AC outputs?” is shown.

4mA: adjust the offset of current output 1 or current output 2.
When the "4mA" function is selected, the device generates a current of 4 mA: measure the current emitted by
the 4-20 mA output using a multimeter and enter the value given by the multimeter in the function "AC1.4mA" or
"AC2.4mA".
20mA: Adjust the span of current output 1 or current output 2.
When the "20mA" function is selected, the device generates a current of 20 mA: measure the current emitted by
the 4-20 mA output using a multimeter and enter the value given by the multimeter in the function "AC1.20mA" or
"AC2.20mA".